Composite Leak Repair (PVC T-Joint) Case Study
Industry Industrial Establishment Technical Details Pipe Material: PVC T-Joint Pipe Size: Dia150mm Pipe Medium: Waste Water Leak Condition: 150mm crack along T-Joint System Pressure: 4 Bar Leak Conditions Leak was found on PVC T-Joint with a crack line of 150mm. The system was holding a pressure of approx. 4 Bar. Repairing the T-joint with standard […]
More -
December 05, 2018
COMPOSITE LEAK REPAIR – NATURAL GAS FLANGE LEAK Case Study
Composite Leak Repair
Details:
More
Leak area: 8inch Valve flange
System Medium: Natural Gas
System Pressure: 2.5Bar
Valve body: Cast Iron
Flange Material: Carbon Steel
Leak Conditions:
A natural gas leak was found on an 8 inch valve’s flange; the system pressure was 2.5 bar. The leakage was detected at 2200hrs. Due to the high risk of ignition and safety for everyone, immediate containment was required.
Traditional Leak Containment Versus Composite Leak Repair due to the medium of the leak, any solution with hot work was not permitted. With the irregular valve body shape, it added another level of difficulty to the repair method. By Using Traditional Leak Containment would require longer lead time to fabricate and install, concurrently the system would be required to shut down. Under this circumstances, resolving the leak immediately was our priority. Therefore, Composite repair methodology was adopted in this scenario. Composite Repair allowed the repair to start immediately and with the added flexibility to seal leak on odd-shaped object. -
July 21, 2017
Leak Repair & Reinforcement Service
Our client is a well-known oil and gas company in Indonesia, with presence in many South East Asian countries. The sump tank at our client’s plant had heavy corrosion, cracks, and leaks. Due to the content of the tank, repair work to stop the leak had to be performed without hot works. For this reason, the client reached out to Alchem for our composite repair solutions.
More -
May 21, 2017
Corrosion Repair and Reinforcement
Our client is a world-class hotel, casino, and theme park integrated resort, located on the well-known tourist attraction of Singapore – the Sentosa island. Our client’s request for our corrosion repair and reinforcement services includes two purposes – to repair the corroded steel structure frames and reinforced concrete (RC) frames and to reinforce the frames with our corrosion repair system solution. This prolongs the life of our client’s theme park attraction structures, lowers their cost of structure replacement, and allows them to serve their customers better by providing safer theme park attractions.
More -
April 20, 2017
Leak Detection Service, Pipe Repair & Reinforcement
Our client is a well-known multinational banking organization headquartered in Singapore, with presence in most Southeast Asian countries. Due to significant leakage and corroded surface area on their existing pipeline system, the client requested a full inspection of the entire pipeline system on every level of their building. This included soil pipes, vent pipes, and kitchen waste pipes. Depending on the inspection results, the client would decide on a pipe replacement or pipe repair solution.
More